Punching Shear in Spread Footings to CSA A23.3

Hatched footing and column with red diagonal lines, one downward arrow and 13 upward arrows
TL;DR Key takeaways before you dive in
  • The common hand calc (whole column load as the shear, no size effect) puts a 3.0 m square footing under 2750 kN factored at 650 mm. CSA A23.3-24 Cl. 13.3.4.3 cuts punching resistance by 16 percent there, so it needs 700 mm.
  • The size effect factor drops away (Cl. 13.3.4.4) when the overhang is under 2d, so punching resistance jumps on deep, compact footings.
  • Subtract the soil pressure inside the critical perimeter; taking the full column load as the shear costs another 50 mm step here.
  • Check one-way shear in both directions. Use 0.21 for beta only if h is 350 mm or less or the overhang is under 2dv, and (under A23.3-24) bars are 500 MPa or less with aggregate of 14 mm or more.
You'll learn:
  • Where the two-way critical perimeter sits in a footing and which soil pressure counts against it
  • Why the 0.38 limit usually governs a square interior column, and when it doesn't
  • How the size effect factor and its 2d footing exemption change the required thickness
  • How to solve for the effective depth in one quadratic and check one-way shear after

Calculations referenced in this post

Pad footing capacity Pro report

Bearing, punching, one-way shear and flexure checks for a pad footing

Open

A 3.0 m square footing under 2750 kN factored comes out at 650 mm with the usual hand calc, which takes the whole column load as the shear and ignores the size effect. Credit the soil under the column and the check even looks comfortable, at a ratio of 0.85. It isn’t, though. Put in the size effect factor and that same footing comes up about 1 percent short, so the answer is 700 mm. CSA A23.3-24 Cl. 13.3.4.3 is the clause that does it.

Thick concrete can’t carry as much shear stress as thin concrete, because the diagonal crack that fails it opens wider before the aggregate on either side can lock together. A footing is about as thick as concrete gets in an ordinary building, so that’s where the reduction bites first.

Where the plug punches out

Picture the column trying to push a plug of concrete out through the bottom of the footing. The crack runs down and outward at roughly 45 degrees, so the plug is a truncated pyramid. The code swaps that sloped surface for a vertical one set d/2 out from each column face (CSA A23.3-24 Cl. 13.3.3.1). Here d is the effective depth to the bottom bars, and with two layers stacked at right angles, punching uses their average, the line where they touch. The dashed square in the sketch is that section, and the vertical dashed line is the one-way shear section, which comes back at the end.

Hatched footing square around a column, with a dashed square and a dashed line, dimensions d/2 and dv

For a square column of side c, that perimeter is \(b_o = 4(c + d)\) long. The soil pushes up over the whole footing, but the pressure inside the perimeter only pushes the plug back up against the column, so it never crosses the crack. The punching shear is just the pressure on the shaded ring outside:

$$V_f = q_f \left[ A - (c + d)^2 \right]$$


Here \(q_f\) is the net factored soil pressure, the column load spread over the footing’s plan area \(A\). Footing and backfill weight push down as hard as the soil pushes back under them, so they drop out. Subtracting the inner square is free resistance, and on this footing it’s worth one 50 mm step of thickness.

How much stress the concrete can carry on that perimeter comes from three equations in Cl. 13.3.4.1, and you take the smallest. All three scale with \(\lambda \phi_c \sqrt{f'_c}\), where \(\phi_c\) is 0.65 and \(\lambda\) is 1.0 for normal-density concrete.

LimitCoefficientWhat it covers
Eq. 13.5\(0.19(1 + 2/\beta_c)\)Long, narrow columns (\(\beta_c\) is the column’s long side over its short side)
Eq. 13.6\(0.19 + \alpha_s d / b_o\)Edge and corner columns (\(\alpha_s\) is 4 interior, 3 edge, 2 corner), or a large column on a thin footing
Eq. 13.70.38The cap for everything else

For a square column the first gives 0.57, and the second stays above 0.38 until the perimeter is about 21 times d. So a square interior column almost always lands on the flat 0.38, or 1.24 MPa at 25 MPa. A column twice as long as it is wide, or an edge or corner column, can change that, so recheck all three once you know d.

Then the size effect factor goes on top of whichever one governs. It’s the lesser of 1 and 1300/(1000 + d), with d in mm, so it starts to bite once d passes 300 mm. At d = 550 mm it’s 0.84, which means a footing that deep loses 16 percent of its punching resistance. That’s about the same as dropping the concrete from 25 MPa to 18 MPa.

Worked example, a 3.0 m footing under 2750 kN

Take a 500 mm square interior column carrying 2750 kN factored onto a 3.0 m square footing, in 25 MPa normal-density concrete with 20 mm aggregate. The bottom mat is 25M each way, fy = 400 MPa, at 75 mm cover. Because the two directions stack, their contact line sits 100 mm above the bottom, so d is h minus 100 mm. You can check whether your own footing thickness passes with the same inputs.

The awkward part is that d sits on both sides, because a deeper footing has a longer perimeter and a smaller shaded ring. Set demand equal to resistance and you get a quadratic in d, with \(v_c\) the governing stress from the table:

$$(4v_c + q_f)\, d^2 + (4v_c + 2q_f)\, c\, d - q_f (A - c^2) = 0$$


The size effect factor sits inside \(v_c\) and depends on d too, so guess d, solve, then update the factor once.

Calculation

Punching shear thickness for a 3.0 m square footing (CSA A23.3-24)

CSA A23.3-24 13.3.4CSA A23.3-24 11.3.6

Concentric load, uniform soil pressure, no shear reinforcement; d = h - 100 mm for two layers of 25M (fy = 400 MPa) at 75 mm cover

Inputs
6 input values\(P_f = 2750\) kN, \(B = 3.0\) m, \(c = 500\) mm ...
\(P_f\)2750kNFactored column load
\(B\)3.0mFooting side (square)
\(c\)500mmColumn side (square)
\(f'_c\)25MPaConcrete strength
\(f_y\)400MPaBar yield strength
\(\phi_c\)0.65Concrete resistance factor
Derivation 8 steps
Step 1: Factored soil pressure\(q_f = 306\ \text{kPa}\)
\[q_f = P_f / B^2\]
\[= 2750 / 3.0^2\]
\(q_f = 306\ \text{kPa}\)
Step 2: Basic punching stress, Eq. 13.7\(v_c = 1.24\ \text{MPa}\)
\[v_c = 0.38 \lambda \phi_c \sqrt{f'_c}\]
\[= 0.38 (1.0)(0.65)\sqrt{25}\]
\(v_c = 1.24\ \text{MPa}\)Eq. 13.5 gives 1.85 MPa for a square column, so 13.7 leads.
Step 3: Try h = 650 mm, size effect factor\(\lambda_s = 0.839\)
\[\lambda_s = 1300 / (1000 + d)\]
\[= 1300 / (1000 + 550)\]
\(\lambda_s = 0.839\)Overhang 1250 mm is more than 2d = 1100 mm, so no exemption.CSA A23.3-24 13.3.4.3
Step 4: Try h = 650 mm, resistance\(V_r = 2390\ \text{kN}\)
\[V_r = \lambda_s v_c \cdot 4(c + d)\, d\]
\[= 0.839 (1235)(4)(1.05)(0.55)\]
\(V_r = 2390\ \text{kN}\)
Step 5: Try h = 650 mm, demand\(V_f = 2410\ \text{kN}\)
\[V_f = q_f \left[ B^2 - (c + d)^2 \right]\]
\[= 305.6 \left[ 9.0 - 1.05^2 \right]\]
\(V_f = 2410\ \text{kN}\)Ratio 1.01, so 650 mm is short.
Step 6: Required d from the quadratic\(d = 0.553\ \text{m}\)
\[(4v_c + q_f) d^2 + (4v_c + 2q_f) c\, d - q_f (B^2 - c^2) = 0\]
\[4449 d^2 + 2377 d - 2674 = 0, \quad v_c = 1036\ \text{kPa}\]
\(d = 0.553\ \text{m}\)Updating the size effect factor at 553 mm moves d to 554 mm. So h = 554 + 100 = 654 mm, round up to 700 mm.
Step 7: Use h = 700 mm, d = 600 mm\(V_r = 2650\ \text{kN}\)
\[V_r = \lambda_s v_c \cdot 4(c + d)\, d\]
\[= 0.813 (1235)(4)(1.10)(0.60)\]
\(V_r = 2650\ \text{kN}\)Overhang 1250 mm is more than 2d = 1200 mm, so no exemption. Eq. 13.5 gives 1.51 MPa and Eq. 13.6 gives 1.94 MPa with the factor, both above 1.00 MPa, so 13.7 still governs.CSA A23.3-24 13.3.4.1
Step 8: Use h = 700 mm, demand\(V_f = 2380\ \text{kN}\)
\[V_f = q_f \left[ B^2 - (c + d)^2 \right]\]
\[= 305.6 \left[ 9.0 - 1.10^2 \right]\]
\(V_f = 2380\ \text{kN}\)
Checks
Punching at h = 650 mmCSA A23.3-24 13.3.4FAIL
\(V_f \le V_r\) : 2410 kN against 2390 kN Demand / capacity1.01
Punching at h = 700 mmCSA A23.3-24 13.3.4PASS
\(V_f \le V_r\) : 2380 kN against 2650 kN Demand / capacity0.90
Watch outWithout the size effect factor, 650 mm shows a ratio of 0.85 and looks comfortable.
Different inputs? Pad footing capacity runs this check with yours. Check your own footing →

Drop the size effect factor and that 650 mm footing reads 0.85, which is why the old answer feels safe. With the factor it reads 1.01, and a 1 percent overrun is still a fail, because the resistance factors already hold the margin you’d be tempted to spend. So use 700 mm, at a ratio of 0.90.

The usual shortcut of taking the whole column load as the shear, inner square and all, is always conservative. With the size effect in, it fails 700 mm too, so at 50 mm steps you’d pour 750 mm, about 7 percent more concrete than the check needs.

Why the resistance jumps at 725 mm

There’s a catch in the other direction. Cl. 13.3.4.4 lets you take the size effect factor as 1.0 for a footing when the point of zero shear sits less than 2d from the column face. Under uniform pressure on a concentric footing, shear dies out at the footing edge, so this post reads that distance as the overhang. The clause doesn’t say it in those words, so confirm your reviewer reads it the same way.

A short, deep cantilever doesn’t really work as a beam, because it carries the soil load by arching straight to the support, the way a masonry wall carries itself over an opening. Arching doesn’t rely on a tight diagonal crack, so the size effect drops out.

Shear versus footing thickness graph with resistance and demand lines and two marked values

So resistance doesn’t climb smoothly with thickness. It jumps at 725 mm. With a 1250 mm overhang the exemption starts at d over 625 mm, or h over 725 mm, which neither trial thickness here reaches, so the full 16 percent loss stays in for both.

One-way shear, and where the check stops

Could one-way shear sneak in ahead of punching? Not on this footing. Treat the footing as a wide beam cantilevering off the column face, with the critical section dv out from the face. Here dv, the effective shear depth, is the larger of 0.9d and 0.72h. The resistance is \(V_c = \phi_c \lambda \beta \sqrt{f'_c}\, b_w d_v\), and beta, the share of shear the cracked concrete carries, is where people go wrong.

Cl. 11.3.6.2 allows the easy 0.21 only when the footing is 350 mm thick or less or the overhang is under 2dv. Even then, the bars must be 500 MPa or less and the aggregate 14 mm or more. Otherwise, for a footing with no stirrups, 400 MPa bars and 20 mm aggregate, Cl. 11.3.6.3 b) gives 230/(1000 + dv), which is a good deal smaller. When steel across a plane carries the shear instead, that’s shear friction.

One-way shear uses each layer’s own d rather than the contact line. The upper layer governs because it sits higher, at d = 587.5 mm and dv = 529 mm. The overhang is more than 2dv, so beta drops to 0.150 instead of 0.21. Run that across the full 3.0 m width beyond the critical section and the footing carries 776 kN against 661 kN of demand. That’s a ratio of 0.85, so punching still governs. A long rectangular footing is different, because the cantilever in its long direction picks up more of the soil load, so run both directions every time.

Everything above assumes a concentric load on an interior column, and each way of leaving that assumption changes the check. A column moment adds shear stress to one side of the perimeter (Cl. 13.3.5). A column on a property line loses one side of the perimeter, or two at a corner, with \(\alpha_s\) dropping to 3 or 2. A steel column on a base plate moves the critical section out from the column face (Cl. 15.5.2). Bars stronger than 400 MPa switch the one-way beta to Eq. 11.9b, which gives 203/(1000 + dv) at 500 MPa. The size effect itself isn’t new in 2024, since A23.3-19 had the same factor and the same 2d exemption, and what 2024 added is the bar and aggregate limit on beta = 0.21. This is also a shear check only, so flexure and minimum steel (Cl. 15.4), bar development and bearing at the column still decide whether 700 mm goes on the drawing.

For a concentric footing, then, the punching check comes down to three moves: subtract the inner square, apply the size effect factor, and compare the overhang with 2d before you accept the loss. That holds while the soil pressure stays uniform. Once a column moment or a property line makes it lopsided, the stress around the perimeter isn’t uniform either, and the quadratic above stops being the answer.

Share this article

Disclaimer: This blog post is for informational purposes only and should not be taken as specific engineering advice. Always consult the latest edition of the National Building Code of Canada and relevant CSA standards for your projects.

Quick answers

Yes. CSA A23.3-24 Cl. 13.3.4.3 multiplies the two-way shear resistance by the lesser of 1 and 1300/(1000 + d), with d in mm. Cl. 13.3.4.4 lets you take it as 1.0 for a footing where the point of zero shear is less than 2d from the column face.
CSA A23.3-24 Cl. 13.3.3.1 places it no closer than d/2 to the column, and Cl. 15.5.2 measures it from the column face. For a square column of side c, the perimeter is 4(c + d).
CSA A23.3-24 Cl. 11.3.6.2 allows 0.21 when the footing is 350 mm thick or less, or when the distance from the point of zero shear to the column face is less than 2dv, provided bars are 500 MPa or less and aggregate is 14 mm or more. Otherwise use 230/(1000 + dv) from Cl. 11.3.6.3.

Next up for you

Standards, Practical Applications

Tension Development Length - Decoding the K-Factors in CSA A23.3

CSA A23.3-24 renamed the K-factors and added a grade factor, so a 25M top bar in 500W steel needs 1501 mm, 39 % more than in 400W. See which …

Keep reading →

Standards, Practical Applications

When Standard Hooks Are Your Only Option

CSA A23.3-24 rewrote the hooked bar equation: a 25M hook at 30 MPa grows from 460 to 721 mm. See how the cover and tie factors win the …

Keep reading →

Design Principles, Professional Development, Practical Applications

Managing Errors in Reinforced Concrete Design: A Philosophy for Engineers

Why managing errors is the mark of skilled RC design in Canada. Understand CSA A23.3 safety factors, phi values, and construction …

Keep reading →
Was this helpful?

Tell us what to cover next or request a deeper dive-every response goes straight to Arun.

Calculations referenced in this post

Pad footing capacity Pro report

Bearing, punching, one-way shear and flexure checks for a pad footing

Open