When Standard Hooks Are Your Only Option

Sketch of a beam bar ending in a standard hook inside a column, with development length l_dh dimensioned
TL;DR Key takeaways before you dive in
  • CSA A23.3-24 Cl. 12.5.2 makes a bare 25M hook in 30 MPa concrete 721 mm long, up from 460 mm under the old rule.
  • A 35M or smaller hook ending in a column core with at least 60 mm of side cover, normal to the hook plane, takes \(k_\ell = 0.8\); enclosing ties with \(A_{th} \ge 0.4 A_{hs}\) take \(k_r = 0.6\), and at a member end only in a column with more than 60 mm of side and top or bottom cover.
  • Both factors together cut the hook to 48 % of the basic length, so detail the joint ties before you size the hook.
You'll learn:
  • How the CSA A23.3-24 Cl. 12.5.2 hook equation differs from the old 100 db / sqrt(f'c) rule
  • Which Table 12.5 factors shorten a hook, and what detailing earns them
  • How to check that a hooked bar fits in an exterior column
  • When to pick a 90 degree or a 180 degree standard hook

Calculations referenced in this post

Hooked bar development length

Required Ld for hooked bars to CSA A23.3-24 Cl. 12.5

Open

Under the old rule, a 25M hook needed about 460 mm. That’s the number most people still carry around. CSA A23.3-24 changed the equation, and the same bare hook in 30 MPa concrete now needs 721 mm. Cl. 12.5.2 sets the new length. That can push a hook out the back of an exterior column.

The good news is that cover and ties win most of it back. Get both and that 25M hook drops to 346 mm.

What changed in the 2024 hook equation

You’d expect a code update to nudge a number by ten percent. This one changed the shape of the equation. A23.3-14 used \(100 d_b / \sqrt{f'_c}\) for 400 MPa bars. The 2024 equation looks like this:

$$\ell_{dh} = \frac{k_\ell k_c k_d k_r f_{yg} d_b^{1.5}}{30 {f'_c}^{0.25}}$$


Here \(d_b\) is the bar diameter and \(f_{yg}\) its grade yield strength. The k terms are modification factors, and a bare hook has them all at 1.0. Bar diameter now enters to the power 1.5, so big bars get hit hardest. Concrete strength enters to the power 0.25, so stronger concrete helps less than it used to.

You’d think a hook is always the short option. At 30 MPa, a bare 35M hook needs 1215 mm. A straight 35M bottom bar with minimum stirrups needs only 1173 mm. So until you earn the factors below, a 35M hook saves nothing, and an old table can’t be patched.

Bar chart of development length by bar size 15M to 35M, comparing old hook rule, new hook rule and straight bars

Where the length comes back: cover and ties

Table 12.5 has two factors that reward good detailing, and they multiply.

FactorValueWhen it applies
Cover0.835M and smaller with side cover, normal to the hook plane, of at least 6 bar diameters, or a hook ending in a column core with at least 60 mm
Ties0.635M and smaller, ties whose legs total at least 40 % of the hooked bar area, or hooked bars spaced at least 6 bar diameters

On the tie route, the code needs two or more ties enclosing the hook, no more than 8 bar diameters apart. Parallel ties must also sit within 10 bar diameters of the bar. Together they cut the hook to 48 % of its basic length, so detail the ties first, then size the hook.

Worked example: a beam hooked into a 600 mm exterior column

Four uncoated 25M bottom bars end in a 600 mm deep column at an intermediate floor. The beam is also 600 mm deep, in 30 MPa concrete. The hook has to stop inside the far column bars, which leaves about 520 mm. The beam is part of a conventional construction frame in the lateral system, so Cl. 12.11.2 wants these bottom bars developed for full yield in tension at the column face. A straight 25M with minimum stirrups would need 828 mm, so it has to hook.

The column is 550 mm wide and the beam 400 mm, so the outer hooks sit about 125 mm in from the column face. That clears the column’s 25M corner bars and leaves plenty of side cover in the core, which earns the cover factor. The column also carries on above, which keeps the top cover clear of the Cl. 12.5.6 limit. But the bars sit about 90 mm apart, under 6 bar diameters, so the tie factor has to come from ties. Five sets of two-leg 10M column ties at 100 mm give 1000 square millimetres of legs, centred on the bars, with two sets below the soffit. That’s 50 % of the hooked bars, and four sets would exactly meet the 40 %. Those ties still have to meet the column and joint tie rules; here they’re only counted for anchorage. Joint shear and the top bar hooks are outside this post.

Calculation

Hooked development of 25M beam bars into a 600 mm exterior column

CSA A23.3-24 12.5.1CSA A23.3-24 12.5.2CSA A23.3-24 Table 12.5

Uncoated 400W bars, normal density concrete, 90 degree hook ending inside the column core, side cover about 125 mm, column 550 mm wide, column continues above, five tie sets centred on the bars, within 10 d_b

Inputs
6 input values\(d_b = 25.2\) mm, \(f'_c = 30\) MPa, \(f_{yg} = 400\) MPa ...
\(d_b\)25.2mm25M bar diameter
\(f'_c\)30MPaConcrete strength
\(f_{yg}\)400MPaBar grade yield strength
\(A_{hs}\)2000mm²Four 25M hooked bars
\(A_{th}\)1000mm²Five sets of 10M ties, two legs each
\(\ell_{avail}\)520mm600 mm column less cover, tie and far column bar
Derivation 4 steps
Step 1: Basic hook length, all factors 1.0\(\ell_{dh} = 721\ \text{mm}\)
\[\ell_{dh} = \frac{f_{yg} d_b^{1.5}}{30 {f^\prime_c}^{0.25}}\]
\[= \frac{400 \times 25.2^{1.5}}{30 \times 30^{0.25}} = \frac{50\,600}{70.2}\]
\(\ell_{dh} = 721\ \text{mm}\)Cl. 12.5.2
Step 2: Column core with about 125 mm side cover\(\ell_{dh} = 577\ \text{mm}\)
\[\ell_{dh} = k_\ell \times 721\]
\[= 0.8 \times 721\]
\(\ell_{dh} = 577\ \text{mm}\)57 mm longer than the column allows.Table 12.5
Step 3: Enclosing ties qualify for the bar arrangement factor\(k_r = 0.6\)
\[A_{th} \ge 0.4 A_{hs}\]
\[1000 \ge 0.4 \times 2000 = 800\]
\(k_r = 0.6\)Table 12.5, Cl. 12.5.4
Step 4: Hook length with both factors\(\ell_{dh} = 346\ \text{mm}\)
\[\ell_{dh} = k_\ell k_r \times 721\]
\[= 0.8 \times 0.6 \times 721\]
\(\ell_{dh} = 346\ \text{mm}\)Table 12.5
Checks
Fit with the cover factor onlyFAIL
\(\ell_{dh} \le \ell_{avail}\) : 577 > 520 mm Demand / capacity1.11
Fit with cover and tie factorsPASS
\(\ell_{dh} \le \ell_{avail}\) : 346 ≤ 520 mm Demand / capacity0.67
Minimum lengthCl. 12.5.1PASS
\(\max(8 d_b, 150) \le \ell_{dh}\) : 202 ≤ 346 mm Demand / capacity0.58
Watch outKeep side cover and top or bottom cover both over 60 mm, or Cl. 12.5.6 takes the tie factor away at this member end.
Different inputs? Hooked bar development length runs this check with yours. Check your own hook →

So the cover factor alone leaves the hook 57 mm too long, and the ties make it fit with about 170 mm to spare. The 302 mm tail fits too. With the 150 mm minimum bend, it tops out about 450 mm above the beam soffit. So put the ties on the drawing with count and spacing, or the 0.6 has nothing behind it.

Beam-column joint sketch: hooked bar needs 346 mm, 520 mm available

90 or 180 degree, and the checks before you pick

Both hooks get the same length, so you pick on fit. What differs is the tail past the bend. CSA A23.1 sets a tail of 12 bar diameters for a 90. A 180 needs only 4, with a 60 mm floor. On a 25M that’s 302 mm against 101 mm.

So use the 90 where the tail can run up the column, and the 180 where depth is tight. The exception is a ductile frame, where Cl. 21.3.3.5 wants a 90 for beam bars ending in a column.

A few things change the answer. Table 12.5 also gives coated bars 1.2 and low-density concrete 1.3. At a member end, Cl. 12.5.6 lets the tie factor apply only in a column with over 60 mm of side cover and top or bottom cover. Where both are under 60 mm, it wants ties no more than 3 bar diameters apart along the hook. The first one goes within 2 bar diameters of the outside of the bend. In a ductile frame, Cl. 21.3.3.5 still sizes the hook by Cl. 12.5, but the bar must also reach the far face of the confined core.

Shear friction dowels hit the same problem on the wall side.

Two rules of thumb for your next joint:

  1. Recompute any hook length taken from a pre-2024 table.
  2. Check hook length plus back cover against the column depth.

To see which factors your own joint earns, check whether your hook fits .

Share this article

Disclaimer: This blog post is for informational purposes only and should not be taken as specific engineering advice. Always consult the latest edition of the National Building Code of Canada and relevant CSA standards for your projects.

Quick answers

CSA A23.3-24 Cl. 12.5.2 gives \(\ell_{dh} = k_\ell k_c k_d k_r f_{yg} d_b^{1.5} / (30 {f'_c}^{0.25})\), with the factors from Table 12.5. Cl. 12.5.1 sets a minimum of \(8 d_b\) or 150 mm, whichever is greater.
No. Cl. 12.5.2 gives the same development length for both. They differ only in the tail: \(12 d_b\) for a 90 degree hook and \(4 d_b\), at least 60 mm, for a 180 degree hook (CSA A23.1 Cl. 6.6.2.2).
No. CSA A23.3-24 Cl. 12.5.7 says hooks are not effective in compression; develop those bars as straight bars to Cl. 12.3.

Next up for you

Design Principles, Professional Development, Practical Applications

Managing Errors in Reinforced Concrete Design: A Philosophy for Engineers

Why managing errors is the mark of skilled RC design in Canada. Understand CSA A23.3 safety factors, phi values, and construction …

Keep reading →

Standards, Practical Applications

Bolt Shear and Tension Resistance to CSA S16-19

Calculate bolt shear, bearing, tear-out and tension resistance to CSA S16-19 Cl. 13.12, with a per-bolt table and a worked four-bolt lap …

Keep reading →

Standards, Practical Applications

Shear Friction Design to CSA A23.3

Size shear friction dowels to CSA A23.3-24 Cl. 11.5: pick c and mu for your joint, solve for the steel, and see what roughening saves at a …

Keep reading →
Was this helpful?

Tell us what to cover next or request a deeper dive-every response goes straight to Arun.

Calculations referenced in this post

Hooked bar development length

Required Ld for hooked bars to CSA A23.3-24 Cl. 12.5

Open